Utility pole sizes: heights, classes, diameters and setting depths

A utility pole is sized by two numbers: its length, in 5 ft steps, and its class, a strength rating set by ANSI O5.1. A 40 ft Class 4 wood pole, for example, is set about 6 ft deep, stands about 34 ft above ground, and is at least 6.7 in across at the top and 10.7 in across 6 ft from the butt. The charts below cover every common length and class.

On Sourcewell Contract #060326-BIDR: wood poles 25 to 70 ft, Class 1 to 5, plus galvanized steel, spun concrete and composite poles, delivered across the contiguous US.

How utility poles are sized

Length sets height. Class sets strength. A spec needs both.

In the US, wood poles are specified under ANSI O5.1, Wood Poles: Specifications and Dimensions. The current edition is O5.1-2022. A pole is called out by length and class together, as in "45 ft Class 3".

The class is a strength rating. Each class is sized to hold a set horizontal load applied 2 ft from the top of the pole. Lower numbers are stronger, the H classes are stronger again, and there is no Class 8. For every length and class, the standard sets two minimum sizes: the circumference at the top, and the circumference 6 ft from the butt (the bottom end).

ClassHorizontal load 2 ft from top (lb)Minimum top circumference (in)Minimum top diameter (in)
H611,4003912.4
H510,0003711.8
H48,7003511.1
H37,5003310.5
H26,400319.9
H15,400299.2
Class 14,500278.6
Class 23,700258.0
Class 33,000237.3
Class 42,400216.7
Class 51,900196.0
Class 61,500175.4
Class 71,200154.8
Class 9740154.8
Class 10370123.8

The top size depends only on class, so every Class 4 pole is at least 21 in around at the top whatever its length. Top diameters here are the circumference divided by π; the Iowa DOT and the Southern Regional Extension Forestry handbook publish the same figures to within 0.1 in. For what each class is generally used for, see the wood utility pole guide.

Utility pole size chart by length and class

Minimum circumference 6 ft from the butt, in inches, by length and class.

This is the ANSI O5.1-2022 table for Douglas Fir and Southern Pine, the two species with an 8,000 psi design fiber strength. A dash means the standard lists no pole of that size.

Length (ft)Class 1Class 2Class 3Class 4Class 5Class 6Class 7
2031.029.027.025.023.021.019.5
2533.531.529.527.525.523.021.5
3036.534.032.029.527.525.023.5
3539.036.534.031.529.027.025.0
4041.038.536.033.531.028.5–
4543.040.537.535.032.530.0–
5045.042.039.036.534.0––
5546.543.540.538.0–––
6048.045.042.039.0–––
6549.546.543.540.5–––
7051.048.045.041.5–––

Weaker species are thicker for the same class. At 40 ft, a Class 4 Western Red Cedar pole is at least 36.5 in around 6 ft from the butt, against 33.5 in for Douglas Fir or Southern Pine; a Class 2 is 42.5 in against 38.5 in.

H-class poles

H classes are used mainly for transmission. Same table, same species:

Length (ft)H6H5H4H3H2H1
2546.044.042.040.038.036.0
3049.547.545.543.041.038.5
3553.050.548.546.043.541.5
4056.053.551.048.546.043.5
4558.556.053.551.048.545.5
5061.058.555.553.050.547.5
5563.560.558.055.052.049.5
6065.562.559.557.054.051.0
6567.564.561.558.555.552.5
7069.066.563.560.557.054.0

These are minimums. Wisconsin Public Service notes that vendors often supply poles above the ANSI minimum, and Caribbean Utilities’ distribution standard caps the excess at 7 in or 20%, whichever is greater.

Utility pole diameter

Minimum diameter 6 ft from the butt, in inches: the ANSI circumference divided by π.

ANSI O5.1 sets circumference, not diameter, because poles are not perfectly round. To get a diameter, divide the circumference by π (about 3.14).

Length (ft)Class 1Class 2Class 3Class 4Class 5
209.99.28.68.07.3
2510.710.09.48.88.1
3011.610.810.29.48.8
3512.411.610.810.09.2
4013.112.311.510.79.9
4513.712.911.911.110.3
5014.313.412.411.610.8
5514.813.812.912.1–
6015.314.313.412.4–
6515.814.813.812.9–
7016.215.314.313.2–

So a 40 ft Class 4 pole is at least 10.7 in across 6 ft from the butt and 6.7 in at the top. A 40 ft Class 1 pole is at least 13.1 in across 6 ft from the butt.

How deep utility poles are set

Depth by length in four utility standards.

Setting depth comes from each utility’s construction standard, not from ANSI O5.1. The standard does list a groundline distance for each length, but says those figures are not recommended embedment depths. Four published utility tables, in feet:

Length (ft)Wisconsin Public Service, firm soilJEA, woodJEA, concretePPL, customer wood pole
20–––4
255––4.5
305.55.565
35666.55.5
406676
456.56.57.56.5
507787
557.57.58.5–
60889–
658.58.510–
709911–
759.59.512–

Wisconsin Public Service adds 1 ft for H-class poles, at least 1 ft in poor soil and at least 1 ft on sloping banks. JEA sets concrete poles deeper than wood. The rule of thumb of 10% of the length plus 2 ft matches these tables at 40 ft (6 ft) but not everywhere: for a 30 ft pole it gives 5 ft, where Wisconsin Public Service and JEA use 5.5 ft. Follow your own standard or an engineer’s pole loading analysis. The wood pole guide covers backfill and soil.

How tall a utility pole is above ground

Pole length minus setting depth, plus typical heights for distribution and transmission.

Height above ground is the pole length minus the setting depth. Using Wisconsin Public Service’s firm-soil depths:

Length (ft)Set depth, firm soil (ft)Height above ground (ft)
25520
305.524.5
35629
40634
456.538.5
50743
557.547.5
60852
658.556.5
70961

Wires sit below the top. In Wisconsin Public Service’s own worked example, a 40 ft pole carries its phase conductor 34 ft above ground and its neutral at 29 ft.

Typical heights by use

UseTypical heightSource
Standard US utility poleAbout 40 ft long, buried 6 ftOak Ridge National Laboratory
Distribution, one Florida utility35 ft Class 4 is its common size; it stopped using 30 ft poles for new distribution in 2009Tampa Electric, Florida PSC filing
Pole presumed for cable and telecom attachment rates37.5 ft, with 13.5 ft of usable spaceFCC rules, 47 CFR 1.1410
138 kV transmission, steel monopolesTypically 75 to 110 ftTucson Electric Power
230 kV transmission, steel poles80 to 115 ftEntergy Louisiana
220 kV tubular steel poles70 to 200 ftCalifornia PUC fact sheet
500 kV lattice towers80 to 215 ftCalifornia PUC fact sheet

Oak Ridge National Laboratory notes that poles can reach 120 ft or more where clearances require it. The FCC’s 37.5 ft is a rebuttable presumption for pole attachment rates, not a construction rule.

Minimum wire height over the ground

NESC minimum clearances that set how tall a pole must be.

Pole height is driven by how high the wires must hang. The National Electrical Safety Code (NESC) sets minimum vertical clearances in Rule 232, Table 232-1. These figures, in feet, are as reproduced in Ameren’s 2022 distribution standard, which cites the 2017 NESC:

WireRoads and streets with truck trafficDriveways, alleys, parking lotsAreas for pedestrians onlyAlong rural roads, not over themRailroad tracks
Neutral, guys, communication15.515.59.513.523.5
Secondary and service, 0 to 750 V16.516.512.514.524.5
Phase, 750 V to 22 kV18.518.514.516.526.5
Phase, 22 to 50 kV19.519.515.517.527.5

Wires sag between poles, so the attachment point on the pole sits higher than these minimums. States can require more: Ameren’s standard requires at least 18 ft over state and federal highways in Missouri and Illinois, citing state rules. Check the NESC edition your state has adopted.

Sizes for steel, concrete and composite poles

Non-wood poles are usually ordered by wood-equivalent class.

Steel, concrete and composite poles are usually ordered by wood-equivalent class, so they can replace a wood pole of the same rating. Snohomish County PUD’s material standard, for example, maps ANSI wood classes to RUS steel pole classes, with the steel tip load set at 0.65 of the wood load (the NESC Grade B strength factor for wood):

ANSI wood classSteel class (RUS)Grade B tip load (lb)
H6S-07.47,410
H1S-03.53,510
Class 1S-02.92,925
Class 2S-02.42,405
Class 3S-02.01,950

Their diameters and weights vary by maker and design, so check the maker’s drawing. See the guides to steel, concrete and fiberglass and composite poles, or compare all four materials.

Pole sizes BIDR supplies on Sourcewell

On Sourcewell Contract #060326-BIDR, BIDR Technologies supplies wood poles 25 to 70 ft in 5 ft steps, Class 1 to Class 5, in Southern Yellow Pine, Douglas Fir and Ponderosa Pine. The BIDR Utilities catalog (opens in a new tab) lists 450 pole specifications, including galvanized steel, spun concrete and composite poles, plus crossarms and line hardware. Pole loading analysis is offered as an engineering service.

  1. Register with Sourcewell. It is free for government and education entities, with no obligation to buy.
  2. Send length, class, material or species, treatment, quantity, delivery site and need date through the utility pole quote form.
  3. Get a written quote at contract pricing, with a delivery timeline.
  4. Issue a purchase order citing the contract number and your agency’s Sourcewell account number.

Your agency stays responsible for its own due diligence. Related guides: utility pole cost and cooperative contracts.

Questions buyers ask

What is the standard size of a utility pole?

There is no single standard size. Oak Ridge National Laboratory describes the standard US utility pole as about 40 ft long and buried 6 ft. Tampa Electric commonly uses 35 ft Class 4 poles for distribution. For cable and telecom attachment rates, FCC rules presume a 37.5 ft pole.

How tall is a 40 ft utility pole above ground?

About 34 ft. A 40 ft pole is usually set 6 ft deep in firm soil, which leaves 34 ft above the ground. Poor soil, slopes and heavier H-class poles call for deeper setting, which lowers the top.

What is the diameter of a utility pole?

It depends on length and class. A 40 ft Class 4 wood pole is at least 6.7 in across at the top and 10.7 in across 6 ft from the butt. A 40 ft Class 1 pole is at least 13.1 in across 6 ft from the butt. ANSI O5.1 sets these as circumferences; divide by π for diameter.

How deep is a 50 ft pole set?

7 ft in firm soil, in the Wisconsin Public Service, JEA and PPL standards. Add at least 1 ft for poor soil or a sloping bank, and more for concrete poles: JEA sets a 50 ft concrete pole 8 ft deep.

Do steel and composite poles use the same classes as wood?

Usually they are ordered by wood-equivalent class, so a steel or composite pole can replace a wood pole of the same rating. Snohomish County PUD, for example, maps a Class 2 wood pole to RUS steel class S-02.4.

Get contract pricing on utility poles

Send length, class, material, quantity and delivery site. You get a written quote at Sourcewell contract pricing with a delivery timeline.

Sources

  1. Pole Dimension Table, ANSI O5.1-2022 Tables 5, 6 and 8 (archived copy) (opens in a new tab), Conrad Forest Products
  2. Electric Distribution Standards, section P: Pole Information (Std P25 setting depth, P30 pole data, P55 pole strength) (opens in a new tab), Wisconsin Public Service
  3. National Wood Pole Standards (ASC O5 overview, Nelson G. Bingel III, ASC O5 Chairman) (opens in a new tab), North American Wood Pole Council
  4. Construction Manual Appendix 12-2: Wood Pole Requirements (opens in a new tab), Iowa Department of Transportation
  5. Service Forester’s Handbook: Pole Specifications (Southern Pine) (opens in a new tab), Southern Regional Extension Forestry
  6. Overhead Electric Distribution Standards, section II.2: Poles (opens in a new tab), JEA
  7. REMSI Sketch 47: Customer wood pole (opens in a new tab), PPL Electric Utilities
  8. Distribution Standards, section 3: Poles (opens in a new tab), Caribbean Utilities Company
  9. Assessment of Commercial Composite Power Pole Performance (ORNL/TM-2021/2068) (opens in a new tab), Oak Ridge National Laboratory
  10. Document 05354-17, Docket 170073-EI: Tampa Electric reply (opens in a new tab), Florida Public Service Commission
  11. 47 CFR 1.1410: Presumptions (pole attachments) (opens in a new tab), Legal Information Institute, Cornell Law School
  12. Kino to DeMoss-Petrie project: pole characteristics (opens in a new tab), Tucson Electric Power
  13. Terrebonne to Bayou Vista 230 kV transmission structures (opens in a new tab), Entergy Louisiana
  14. Transmission Structures fact sheet (Aspen Environmental Group) (opens in a new tab), California Public Utilities Commission
  15. Distribution Construction Standards, section 29: Overhead Lines Instructions (DCS 29 00 17 02, vertical clearance of wires) (opens in a new tab), Ameren
  16. Material Standard 5000170.1: Wood Class Equivalent Ductile Iron and Steel Utility Poles (opens in a new tab), Snohomish County PUD
  17. Solicitation 11229: Utility Poles (awarded contracts) (opens in a new tab), Sourcewell
  18. How cooperative purchasing works (opens in a new tab), Sourcewell
  19. Supply Catalog (opens in a new tab), BIDR Utilities